System Part Number: 900-0782-81, -91
Document P/N: 551-0782-81, Rev C1
December 2014
Installation Guide
Peninsula Engineering Solutions may change specifications as necessary to meet industry requirements. © 2014 Peninsula Engineering Solutions, inc.
Either screen can be used to read the RSSI value, the Basic Radio Interface Stats may be
quicker to update.
Note: this Basic Stats screen does not display real RSSI (shows -120 dBm only)
at the RF Repeater (UHF Telemetry Transmitter, MDS set to “Single Root
Remote”) end – the RSSI/Zone Statistics screen must be used instead.
Adjust the UHF antennas for best RSSI. Target is -95 dBm or more. Threshold is -106 dBm for
10
-06
BER.
Transmitter Setup
Start at the NETio Main Menu and type ‘C’ Wireless Configuration. Then type ‘A’ entraNET
Configuration.
Type ‘A’ Basic Configuration, and then select the item to configure.
Selection Item Description
A Unit
ID for base and associated expansion modules. Defaults to the last 4 digits of the base serial number
†
.
Can be changed as necessary. Must be unique on the same network.
If replacing a failed base module, recommend changing the ID to the previous unit’s ID.
This eliminates changes to far end point mapping.
B
Network
Address
All units on the same network must use the same address. Both ends of the
RMAS-120-81 UHF Telemetry Link must use the same address. Select as desired.
C Output Power +20 to +30 dBm in 1 dB steps.
D Band 2400 MHz only, select A, B or C. Transmitter and Receiver must match.
Peninsula Engineering Solutions, inc. Telephone +1 925 837-2243
POB 1095 Facsimile +1 925 837-2298
Danville, California 94526, USA Internet www.peninsulaengineering.com